Take an online course or view a seminar right from your office. Our partner, Stationary Battery Training, offers 44 Battery Training Courses and Reference Tools and many seminars with associated quizzes to be sure staff is fully trained in standby power systems. Go to StationaryBatteryTraining.com for more information

Contact Information

ESA Consulting Associates, Inc.

PO Box 9251
Jupiter, Florida 33468-9251
Phone +1.561.691.1946
Fax +1.561.691.1454
Email marco@esaconsulting.com

Monthly Archives: June 2015

//June

Verification of Battery Continuity and NERC Std PRC-005

By |June 28th, 2015|Stationary Battery Forum – All Industries|

NERC Std PRC-005, Protection System Maintenance requires that battery continuity be verified every 18 months for all batteries, not having the monitoring attributes of Table 1-4(f).  See Tables 1-4(a), 1-4(b) and 1-4(c) for vented lead-acid, valve regulated and nickel-cadmium batteries, respectively, in revision 2 of the standard which is the current version in force.  The [...]

Installation 1

By |June 15th, 2015|Is Something Wrong Here?|

Is there anything wrong with this installation?  To enlarge photo, right click the photo and select "Open link in new tab". Post your responses now!

Hydrogen Evolution – Where Did The Value In IEEE Std 484TM Come From?

By |June 15th, 2015|Stationary Battery Forum – All Industries|

IEEE Std 484TM – 2002 states that the maximum hydrogen evolution rate for an electrochemical cell is 0.000269 ft3/min per charging ampere per cell at 77 °F and standard pressure (29.92 in Hg) or 0.127 mL/s per charging ampere per cell at 25 °C and standard pressure (760 mm Hg).  This has been in the [...]

Ripple Voltage and Current and Their Effects on Stationary Batteries

By |June 15th, 2015|Stationary Battery Forum – All Industries|

Questions on ripple continue to come up, particularly for vented lead-acid cells and nickel-cadmium cells; however, there is little information available on the subject.  One US battery manufacturer has included some information on ripple voltage  for its vented lead-acid products in its most recent Installation, Operation and Maintenance Instructions issued in February 2015.  The other [...]

Spill Containment Requirements – 2015 Codes

By |June 10th, 2015|Stationary Battery Forum – All Industries|

There are always questions regarding the requirements for spill containment for vented cells.  The current standards discuss spill containment requirements and the requirements for neutralizing separately.  It's clear in the current standards that for valve regulated lead acid cells spill containment is not required for VRLA installations; however, there are still requirements for neutralizing. An excerpt of [...]

Exposure of Cell Plates Due to Elevated Temperatures – Fukushima Events

By |June 10th, 2015|Nuclear Plant Battery Forum|

There have been recent questions posed to plants about possible exposure of the cell plates due to elevated battery temperatures as part of the various conditions and scenarios for the Fukushima type events.  The beyond design basis events typically result in elevated temperatures throughout the plant, including the battery rooms.  The concern is an increased water [...]